Hermetic filter drier, DML, 16

Danfoss

Product code: 023Z5044
PLEASE LOGIN TO SEE PRICES
Product Group : Liquid Line Driers
General Information
Activated Alumina / Molec. Sieve. : 0/100 %
Product Group : Liquid Line Driers
Specification Key : DML 164
Type : DML 164
Additional Info
Family : DML
Capacity
Acid Capacity : 1.20 g
Capacity : R32: 40.5 kW, R134a: 26.6 kW, R404A: 18.7 kW, R407C: 27.2 kW, R410A: 27.7 kW, R507: 18.1 kW
Liquid Capacity Conditions (ARI 710-2009) : Delta p=0.07bar, tliq= 30°C, tvap=-15°C
Connections
Connection Size : 1/2"
Connection Type : Flare
Inlet Type : Flare
Outlet Type : Flare
Driers
Core : Solid core
Core Size : 16 cu.in.
Flow Capacity kW : R32: 40.5, R134a: 26.6, R290: --, R404A: 18.7, R407C: 27.2, R410A: 27.7, R507: 18.1
Shell Volume : 0.35 L
Solid Core Surface : 28.34 in², 183 cm²
Solid Core Volume : 7.84 in³, 128 cm³
Drying Capacity
Drying Capacity 24°C (Drops of Water) : R32: 470, R134a: 559, R290: --, R404A: 582, R407C: 543, R410A: 506, R507: 610
Drying Capacity 52°C (Drops of Water) : R32: 433, R134a: 512, R290: --, R404A: 551, R407C: 500, R410A: 450, R507: 548
Logistical Information
Commodity Code : 84212980
Country Of Origin : MEX
EAN : 5702428155687
Gross Weight : 0.935 kg
Material
Body Material : Steel
Connection Material : Steel
Measurements
Net Weight : 0.74 kg
Volume : 0.226 L
Weight : 0.74 kg
Oil
Oil Type : Oilfree applications
Pressure
Max Operating Pressure : 46.0 Bar
Refrigerant
Refrigerant : R22/R407C, R23, R32, R125, R134a, R404A, R407A, R407F, R407H, R410A, R422B, R422D, R438A, R444B, R448A, R449A, R449B, R450A, R452A, R452B, R454A, R454B, R454C, R455A, R463A, R507A, R513A, R515B, R516A, R1233zd(E), R1234yf, R1234ze(E)
Standards
Approval : UL
Temperature
Max Temperature : 70 °C
Medium Temperature Range : -40-70 °C
Min Temperature : -40 °C
Temperature Range : -40-70 °C
Valves
Flow Direction Indicator : Label printed 1-way arrow
Fluid Group : 2
Filter drier DML 164 M/12