Capacity R448A/449A
| R448A/449A Capacity -20°C : | 14.69 kW |
|---|---|
| R448A/449A Capacity 0°C : | 18.96 kW |
| R448A/449A Capacity 10°C : | 18.22 kW |
Cooling Capacity R448A/R449A
| R448A/R449A Cooling Capacity -10°C : | 18.8 kW |
|---|
Cooling Capacity R507
| R507 Cooling Capacity Rated -10°C : | 13.84 kW |
|---|
Nominal Capacity R448A/R449A
| R448A/R449A Nominal Capacity : | 19.44 kW |
|---|
Nominal Capacity R507
| R507 Nominal Capacity : | 14.2 kW |
|---|
R1234yf Performances
| R1234yf Capacity -10°C : | 7.75 kW |
|---|---|
| R1234yf Capacity -20°C : | 5.82 kW |
| R1234yf Capacity 0°C : | 7.78 kW |
| R1234yf Capacity 10°C : | 7.51 kW |
R134A Performances
| R134A Capacity 10°C : | 10.72 kW |
|---|---|
| R134a Capacity -10°C : | 11.43 kW |
| R134a Capacity -20°C : | 8.74 kW |
| R134a Capacity 0°C : | 11.43 kW |
| R134a Cooling Capacity Rated -10°C : | 10.98 kW |
| R134a Nominal Capacity : | 11.7 kW |
R404A Performances
| R404A Capacity -10°C : | 13.49 kW |
|---|---|
| R404A Capacity -20°C : | 10.29 kW |
| R404A Capacity -30°C : | 7.25 kW |
| R404A Capacity -40°C : | 5 kW |
| R404A Capacity 0°C : | 13.43 kW |
| R404A Capacity 10°C : | 12.89 kW |
| R404A Cooling Capacity Rated -10°C : | 13.84 kW |
| R404A Nominal Capacity : | 14.2 kW |
R407C Performances
| R407C Capacity -10°C : | 20.74 kW |
|---|---|
| R407C Capacity -20°C : | 15.31 kW |
| R407C Capacity 0°C : | 20.62 kW |
| R407C Capacity 10°C : | 19.88 kW |
| R407C Cooling Capacity Rated -10°C : | 20.64 kW |
| R407C Nominal Capacity : | 21.1 kW |
R407F Performances
| R407F Nominal Capacity : | 21.8 kW |
|---|
R448A/R449A Performances
| R448A/449A Capacity -10°C : | 19.2 kW |
|---|---|
| R448A/449A Capacity -30°C : | 9.96 kW |
R452A Performances
| R452A Capacity -10°C : | 14.04 kW |
|---|---|
| R452A Capacity -20°C : | 10.56 kW |
| R452A Capacity -30°C : | 7.02 kW |
| R452A Capacity -40°C : | 4.5 kW |
| R452A Capacity 0°C : | 14.07 kW |
| R452A Capacity 10°C : | 13.67 kW |
R454C Performances
| R454C Capacity -10°C : | 15.31 kW |
|---|---|
| R454C Capacity -20°C : | 11.7 kW |
| R454C Capacity 0°C : | 15.22 kW |
| R454C Capacity 10°C : | 14.83 kW |
R455A Performances
| R455A Capacity -10°C : | 19.2 kW |
|---|---|
| R455A Capacity -20°C : | 14.69 kW |
| R455A Capacity -30°C : | 9.96 kW |
| R455A Capacity 0°C : | 18.96 kW |
| R455A Capacity 10°C : | 18.22 kW |
R513A Performances
| R513A Capacity -10°C : | 10.09 kW |
|---|---|
| R513A Capacity -20°C : | 7.74 kW |
| R513A Capacity 0°C : | 10.07 kW |
| R513A Capacity 10°C : | 9.67 kW |
The nominal cooling capacity kW is given at an evaporating temperature of +4°C, a condensing temperature of +38°C and 1 K subcooling at the inlet of the expansion valve.